Main Electrical Service
Monitoring two 3ph breakers


 
Loads

Meters

MeterValue
L1-N282.5V
L2-N281.9V
L3-N283.4V
N-E0.07V
L1-L2487.9V
L2-L3489.6V
L3-L1490.8V
L1 Amp63.61A
L2 Amp58.75A
L3 Amp65.37A
N Amp16.98A
E Amp0.0002A
L6 Amp16.32A
L7 Amp10.09A
L8 Amp17.60A
Frequency60.001Hz
L1-N Voltage Fundamental282.4V
L1 Voltage Fundamental Angle0.00deg
L2-N Voltage Fundamental281.8V
L2 Voltage Fundamental Angle240.36deg
L3-N Voltage Fundamental283.3V
L3 Voltage Fundamental Angle120.30deg
L1 Current Fundamental63.33A
L1 Current Fundamental Angle-31.05deg
L2 Current Fundamental58.52A
L2 Current Fundamental Angle211.63deg
L3 Current Fundamental65.41A
L3 Current Fundamental Angle86.70deg
 
Energy/Power

MeterValue
PowerTotal45.389kW
L115.342kW
L214.519kW
L315.528kW
Apparent PowerTotal53.176kVA
L117.976kVA
L216.547kVA
L318.652kVA
True Power FactorTotal0.853
L10.853
L20.877
L30.832
Reactive PowerTotal27.704kVAR
L19.369kVAR
L27.937kVAR
L310.335kVAR
Energy
(since 2018/12/21)
162.037155MWh
Energy Imported
(since 2018/12/21)
162.037415MWh
Energy Exported
(since 2018/12/21)
-0.250552kWh
Apparent Energy
(since 2018/12/21)
177.977MVAh
Reactive Energy
(since 2018/12/21)
68.552MVARh
Positive Reactive Energy
(since 2018/12/21)
68.552MVARh
Negative Reactive Energy
(since 2018/12/21)
-0.001kVARh
Peak RMS Current
(since 2018/12/21)
1 cycle162.57Arms
1 minute96.73Arms
15 minute89.65Arms
Peak Power
(since 2018/12/21)
1 cycle104.822kW
1 minute65.228kW
15 minute58.577kW
Peak Apparent Power
(since 2018/12/21)
1 cycle128.162kVA
1 minute77.337kVA
15 minute68.667kVA
 
ClassA

MeterValue
Flicker (L1-N)Pinst0.01
PST0.11
PLT0.09
Flicker (L2-N)Pinst0.00
PST0.12
PLT0.09
Flicker (L3-N)Pinst0.00
PST0.10
PLT0.09
Max 2kHz-9kHz0.14V @ 2.6kHz(L1-E)
Max 8kHz-150kHz0.14V @ 54kHz(L3-E)
THD-V L1-N1.07%
THD-V L2-N0.95%
THD-V L3-N0.91%
TDD-A L12.33%
TDD-A L20.88%
TDD-A L30.69%
V Unbal Zero Seq0.04%
V Unbal Neg Seq0.35%
I Unbal Zero Seq4.50%
I Unbal Neg Seq3.66%
 
Harmonics

MeterL1-NL2-NL3-NL1 AmpL2 AmpL3 Amp
H3 0.2%0.3%0.1%4.40A1.51A0.69A
H5 0.4%0.6%0.4%0.87A0.33A0.32A
H7 0.8%0.6%0.7%0.95A0.72A1.09A
H9 0.1%0.1%0.1%0.48A0.29A0.13A
H11 0.4%0.4%0.3%0.14A0.07A0.10A
H13 0.0%0.1%0.1%0.19A0.20A0.19A
H15 0.1%0.1%0.1%0.23A0.08A0.13A
H17 0.1%0.1%0.1%0.31A0.13A0.04A
 
ENV Roof

MeterValue
Temperature36.0°C
Humidity22.3%RH
Pressure1017.93hPa
Probe A X Acceleration-0.019m/s²
Probe A Y Acceleration-0.010m/s²
Probe A Z Acceleration-0.010m/s²
Probe A Vector Acceleration0.018m/s²
 
ENV Wall

MeterValue
Temperature23.7°C
Humidity49.4%RH
Pressure1017.64hPa
Probe B X Acceleration-0.010m/s²
Probe B Y Acceleration-0.019m/s²
Probe B Z Acceleration-0.010m/s²
Probe B Vector Acceleration0.019m/s²
 
 