Under-frequency - Powerside - Alameda, California, Harbor Bay Drive

PQube 3 Information

Location:Powerside - Alameda, California, Harbor Bay Drive
PQube 3 ID:PQube 3 - Power Quality & Power Flow
Note 1:Engineering Lab
Note 2:Monitoring two 3ph breakers
PQube 3 Serial Number:P3001692
Model Number:PQube 3
Firmware Version:3.10.8.24.07.23
Time Zone:PDT
 
Configuration

Power Configuration:Wye/Star
Nominal Line-to-Neutral Voltage:120.0V
Nominal Line-to-Line Voltage:208.0V
Nominal Frequency:60Hz
Potential Transformer Ratio:1:1
Current Transformer Ratio:600:1
 
Event

Event Type:Under-frequency
Event Magnitude:59.52Hz
Event Duration in Seconds:2.132
Trigger Date:2025/03/17
Trigger Day of Week:Monday
Trigger Time:T 06:14:00.051 PDT
Trigger Channel:Frequency
Trigger Channel ID:21
Trigger Threshold:99.5% of nominal
 
Min Max Readings

ChannelMinMaxMin
During Event Only
Max
During Event Only
N-E2.46V2.46V2.46V2.46V
L1-N61.0V122.5V122.0V122.5V
L2-N121.9V122.5V122.0V122.5V
L3-N122.4V123.1V122.6V123.1V
L1-L2109.3V211.9V211.1V211.6V
L2-L3212.3V213.6V212.3V213.4V
L3-L1103.4V212.6V211.8V212.4V
L1 Amp0.14A292.90A233.85A268.00A
L2 Amp226.41A261.20A233.67A249.96A
L3 Amp226.71A272.19A238.56A256.65A
N Amp0.00A0.00A0.00A0.00A
E Amp0.0000A0.0000A0.0000A0.0000A
L6 Amp0.00A0.00A0.00A0.00A
L7 Amp0.00A0.00A0.00A0.00A
L8 Amp0.14A0.14A0.14A0.14A
Frequency59.517Hz59.981Hz59.517Hz59.980Hz
Power48.047kW100.913kW86.425kW96.368kW

Data from the Powerside PQube® 3 by www.Powerside.com